Case Details

Detalles del caso

Proyecto de tratamiento de agua potable de 57,6 m³/h en Rumanía

Resumen del proyecto

Artículo Detalles
Nombre del proyecto Proyecto de tratamiento de agua potable
Ubicación Motatei, Romania
Año May 2019
Water Source Deep well water from 6 wells
Total Capacity 57.6m³/h
System Configuration Carbon Filter + Ion Exchange / Carbon Filter + RO
Container Type 40HQ FLC
Control Method Remote control

Antecedentes del proyecto

The raw water came from six deep wells in Romania. Several water quality indicators exceeded the required limits, including ammonia, nitrate, E. coli, total bacterial count, iron, and manganese. Among these issues, nitrate was the most critical, while ammonia, iron, and manganese were slightly above standard limits.

To meet drinking water requirements, the project adopted a combined treatment process. Disinfection and activated carbon filtration were used to handle microbial indicators and slightly excessive ammonia, iron, and manganese. RO treatment was applied to reduce nitrate levels, while ion exchange water and RO permeate were blended to achieve the required final water quality.

Solución de tratamiento

The project uses two parallel treatment lines:

  • Carbon Filter + Ion Exchange System: 28.8m³/h
  • Carbon Filter + RO System: 28.8m³/h

The RO permeate and ion exchange product water are mixed to produce drinking water. The system design supports stable output while maintaining suitable nitrate and hardness levels in the final blended water.

Drinking Water Treatment Project in Romania-3

Flujo de procesos

Ion Exchange Line

Raw Water Tank → Raw Water Pump → Activated Carbon Filter → Ion Exchanger → Product Water Tank

RO Line

Raw Water Pump → Activated Carbon Filter → Security Filter → High Pressure Pump → RO Unit → Product Water Tank

Sistemas de apoyo

  • Antiscalant dosing system
  • Chemical cleaning system
  • Disinfection dosing system
  • Remote control system

Principales resultados

  • Total water production capacity: 57.6m³/h
  • RO system product water nitrate: <12.15mg/L
  • RO system hardness: <2.8mg/L as CaO
  • Final blended water nitrate: <28.8mg/L
  • Final blended water hardness: >6.85mg/L
  • Final water quality meets drinking water requirements

Drinking Water Treatment Project in Romania

Proyectos destacados

  • Containerized integrated design in one 40HQ FLC
  • Combination of RO and ion exchange treatment
  • Blended water production for drinking water use
  • Remote control for easier operation

Drinking Water Treatment Project in Romania-1

Aplicaciones

  • Well water drinking treatment
  • Groundwater purification
  • Municipal and decentralized water supply
  • Containerized drinking water systems

Solicitar presupuesto